Warm air under the roof

Warm air rises and collects under the roof, where it costs the most. See how much of the heat bill stratification accounts for, and what mixing the air saves.

Warm air is lighter than cold air, so in a heated hall it rises and collects under the roof. Without anything to move it, the air gets warmer the higher up you go. In a heated hall the rise is typically 0.3–0.5 K per metre, and more with warm-air heaters. At 0.4 K per metre, the air under the ridge of a 9 m hall is 3.6 K warmer than the air where people work.

That warm layer does nobody any good, and it costs. The roof loses heat in proportion to the difference between the air under it and the air outside, so every extra degree under the roof is paid for on the heating bill. The upper part of the walls loses more for the same reason.

Large, slow ceiling fans (HVLS) push the warm air gently back down and mix the hall to one temperature. That has two effects:

  1. The roof and the upper walls see air at the temperature of the floor instead of the warm layer, so they lose less.
  2. The floor gets the warm air back, so the thermostat can be turned down 1–2 K for the same comfort.

Stratification and mixed air

m

The highest point under the roof. Equal to the wall height for a flat roof.

K/m

How much warmer the air gets for each metre up, without fans. 0.3–0.5 K/m is typical for a heated hall; with warm-air heaters it can reach 1 K/m.

K

Once the air is mixed, the floor is warmer, so the thermostat can be turned down. 1–2 K is typical.

More settings
°C
m
m
m

Sets typical U-values for the age of the building. You can change each one below.

W/m²K
W/m²K
W/m²K
W/m²K
W/m²K
%
%
K

Degrees kept warm by people, lighting, machines and the sun.

°C
K·d

K·days below 17 °C over the heating season. Typical for the chosen country.

days
EUR/MWh

Per MWh of heat delivered, boiler or heat pump efficiency included. Typical for the country and heating.

kg/MWh

Results

Air under the roof22.9 → 18.0 °Cat the mean roof height, 7.3 m
Heat saved13.4 MWh30 % of the envelope’s loss
Saved1,070 EURper year
CO₂e avoided1.01 tper year
18.020.022.024.00.04.59.0Air temperature, °CHeight, m18.0 °C23.6 °C
Air temperature from floor to ridge, stratified and mixed
Heat lost per year by surface, kWh
Stratified (today)Mixed air (HVLS)
Roof15,0009,870
Walls14,10010,300
Windows9,3806,860
Floor7,0605,040
Heat lost per year by surface, kWh

The air under the roof is 22.9 °C. Mixing it saves 13.4 MWh a year, 30 % of the envelope’s loss, or 1,070 EUR per year.

Indicative calculation based on the assumptions shown. How we calculate · Contact us for a calculation of your building.

The higher the hall and the stronger the stratification, the more there is to save. In a low hall with little stratification, most of the saving comes from the lower setpoint.

How we calculateLast subject-matter review: 20 October 2026

Formulas

The transmission loss of each surface is calculated as in U-values and heat loss, twice:

  • Stratified (today): the floor at the setpoint TsetT_\text{set}, the roof at Troof=Tset+g hˉT_\text{roof} = T_\text{set} + g\,\bar h where gg is the gradient and hˉ\bar h the mean roof height, and the walls at (Tset+Troof)/2(T_\text{set} + T_\text{roof})/2.
  • Mixed air (HVLS): every surface at Tset−ΔTspT_\text{set} - \Delta T_\text{sp}, where ΔTsp\Delta T_\text{sp} is the setpoint reduction.

The saving is the difference between the two over the heating season:

ΔQ=∑i(Qistratified−Qimixed)\Delta Q = \sum_i \left( Q_i^\text{stratified} - Q_i^\text{mixed} \right)

Assumptions

  • The temperature rises in a straight line from floor to roof before, and the fans mix the hall completely after. In practice a small gradient remains with the fans running, so for the same inputs the saving is an upper estimate.
  • The free heat (people, lighting, machines, the sun) is the same before and after, so it changes the totals but not the saving.
  • The fans’ own electricity, ventilation and cooling in summer are not included here.

Range of validity

Heated halls with a ceiling height of 4–25 m. The gradient is an input: measure it, or use 0.3–0.5 K/m for a hall heated with radiators or floor heating and up to 1 K/m with warm-air heaters.

Standards and sources

  • U-values of building components: EN ISO 6946. Thermal comfort and draught: EN ISO 7730.
  • The method follows the Nordicco template for energy calculations, the same calculation the Nordicco sales team uses for quotes (engine crm-energy-1.7).